In article <
dtd94k+6ej7@...>,
dl5012 <
dl5012@...> wrote:
> You should always ground the chassis of your equipment to earth
> ground.
Absolutley
> The neutral line will be connected to earth ground at the
> circuit breaker, so you don't need to connect it yourself; but many
> will to make sure that the path to earth ground is as short as
> possible.
If I understand correctly what you are saying here the answer is no, no,
no.
You /must never/ connect the incoming neutral to earth within any piece of
equipment you build.